Abstract:A fresh air supply system is often necessary in winter to enhance indoor air quality in underfloor heating rooms, making the selection of air supply parameters particularly important. Computational fluid dynamics simulations were employed to investigate the effects of supply air temperature and supply angle under mixed ventilation on the formaldehyde removal efficiency and indoor thermal comfort in an underfloor heating room. The study set the release of formaldehyde from the office desk, and different combinations of supply air angles (30°, 60°, 90°) and supply air temperatures (10, 15 and 20 °C) were considered. Based on the simulation results, distribution characteristics of air flow velocity, temperature, predicted average rating minus predicted dissatisfaction percentage indicator (predicted mean vote and predicted percentage of dissatisfied, PMV-PPD) and formaldehyde mass fraction on different vertical planes and in the ankle activity region were analyzed. Quantitative calculations of the head-to-foot temperature difference and formaldehyde removal efficiency indicators were also conducted. The research results indicate that when the supply air angle is constant, an increase in supply air temperature reduces the temperature difference between the floor and the supply air, the thermal buoyancy effect weakens, leading to a decrease in airflow velocity. When the supply air temperature is constant, the change in the supply air angle affect the flow path of the fresh air, thereby altering the distribution of vortex airflow. An increase in supply air temperature will increase the indoor temperature. The indoor temperature distribution is closely related to the air flow velocity distribution, high-temperature areas often occur in low-velocity air flow zones. The calculation of head-to-foot temperature difference indicates that the indoor thermal comfort meets the first-level satisfaction standard. The PMV-PPD indicates that when the supply air temperature is 20 °C and the supply air angle is 60°, the proportion of the first-level comfort zone in the indoor space is the largest. The best formaldehyde removal efficiency is achieved at a supply air temperature of 15 °C and a supply air angle of 30°.