Abstract:Air source heat pumps present high efficiency and environmental benefits, but they face frosting issues during winter operation. A binary hydrated salt composite was integrated into the CO2 air source heat pump system for dehumidification and frost mitigation. The composite material was synthesized by vacuum impregnation of LiCl/CaCl2 into Wakkanai siliceous shale, and experimental results show that the 4LiCl/CaCl2 formulation exhibits the strongest dehumidification performance. A dehumidification device was developed and tested based on this material and applied to a CO2 air source heat pump system for simulation studies. Simulation results under different outdoor temperatures (?4 to 0 ℃) indicate that the evaporation temperature, heat exchange capacity, outlet water temperature, and coefficient of performance are increased by a maximum of 1.0 ℃, 15.9%, 2 ℃, and 5.3%, respectively. The binary hydrated salt composite can effectively improve the performance and operational stability of CO2 air source heat pump systems under low-temperature and high-humidity conditions. The research provides a promising material solution to address the winter performance degradation of CO2 air source heat pump systems.